For your specialized temperature controller needs, our experienced staff of sales engineers can help you with equipment design and modification. | Chiller Description A BERG line commercial cooling unit, modified to meet the requirements specified. The unit shall be designed to operate on sea shore site and on ship deck when subjected to the sea environmental conditions. The unit shall supply cold coolant – solution of Ethylene Glycol and distilled water – to a consumer located about 25 meters away from the cooling unit. The unit framework shall be strengthening to allow tying the unit to the deck with cables. Coolant Type The coolant shall be a solution - by weight – of 30% Ethylene-Glycol and 70% Distilled Water, with additive inhibitors, for use with bare Aluminum heat exchangers and Stainless Steel pipes and components. The refrigerant used is environment friendly substance type R-134a Cooling Capacity The total cooling capacity of the chiller shall be based on the following: Consumer heat load (70 kW) + ambient heat load + solar radiation heat load +internal heat load generated by the pumps. Flow Rate A nominal flow rate of 50 gpm @ pressure of 115+/-5 psid @ temperature of 18C Working pressure The external working pressure required is 115+/-5 psid nominal, measured between the Chiller outlet and inlet. |